7505A0000U BECKETT GENISYS ADVANCED OIL BURNER PRI

651405 MFG #: 7505A0000UBECKETT
$0.00 / ea
  • 120 VAC advanced burner control is a primary safety control for residential and light commercial oil burners used in boiler, furnace, and water heater applications
  • The GeniSys is used with a suitable cad cell flame sensor to control the oil burner motor, igniter and optional solenoid valve
  • It has 24 VAC thermostat inputs compatible with both on/off and power stealing thermostats
  • Provide interrupted or intermittent duty ignition and has a 15 sec lockout time
  • Thermostat and boiler control compatible
  • Programmable valve-on delay and motor-off delay
  • Three indicator lights for system monitoring and diagnostics
  • Two communication ports for adding alarm contacts, programming display and/or future wireless communications
  • Welded relay protection with redundant motor relays
  • Limited reset and limited recycle
  • Sleek, modern design
  • Technician pump prime mode
  • Customizable pre-time and post-time
  • 5-year warranty
  • Replaces R7184A, R8184G
QTY
  • Specifications
Storage And Operating Temperature
-40 To 150 deg F
Amperage Rating
100 milli-amp Plus Burner Motor, Igniter And Valve Loads/Motor: 10 (FLA), 60 (LRA)
Frequency
60 Hz
Moisture
5 To 85 PCT RH, Non-Condensing And Non-Crystallizing
Thermostat Anticipator Current
0.1 amp
Thermostat Voltage
24 VAC
Sub Brand
GeniSys™
Voltage Rating
Input: 102 To 132 VAC, Output: 120 VAC
Standards
UL372, 1998 And CSA-B140.0
Sub Brand
GeniSysâ„¢
Ignitor
120 VAC, 3 amp At 0.7 PF min
Solenoid Valve